I. Operating Principle
(I) Generation of Reactive Power
The charge between the plates of a capacitor undergoes repeated charging
and discharging cycles in response to the polarity of an alternating voltage.
This causes the current phase to lead the voltage by approximately 90°,
manifesting as capacitive reactive power within the circuit. The reactive power
(Q) is directly proportional to the frequency (f), capacitance (C), and the
square of the voltage (U): Q = 2πfCU². This explains why the capacity of the
same capacitor can vary drastically at different frequencies—for instance, a 100
µF capacitor yields approximately 5 kVAR at 400 V and 50 Hz, but reaches 300
kVAR at 3 kHz. This is precisely why capacitors used for induction heating must
be purpose-designed.
(II) Formation of a Parallel Resonant Tank Circuit with the Induction
Coil
A capacitor bank (C) connected in parallel with an induction coil (L) forms
a parallel resonant tank circuit, with a resonant frequency of f₀ = 1/(2π√(LC)).
At the point of resonance, the inductive current and capacitive current cancel
each other out; the power supply only needs to compensate for the active power
losses within the tank circuit, resulting in a power factor close to 1. Taking L
≈ 20 µH and C ≈ 100 µF as an example, the resonant frequency is approximately
3.6 kHz, and the characteristic impedance is about 0.45 Ω—a value roughly
equivalent to the capacitive reactance of the capacitor at the resonant
frequency. At this stage, the circulating current within the resonant circuit
can reach several times the magnitude of the power supply's output current. It
is precisely this circulating current that establishes a strong alternating
magnetic field within the induction coil—a field sufficiently intense to melt
metal.
(III) Energy Exchange Between Electric and Magnetic Fields
Within each cycle, energy oscillates between the electric field of the
capacitor and the magnetic field of the induction coil. In effect, the capacitor
functions as a "reactive power relay station": it supplies the necessary
reactive power locally to the induction coil, preventing this power from having
to travel back and forth between the power supply and the load. This reduces the
required capacity of the power supply and minimizes line losses.

(IV) Losses and Heat Generation
Operating losses stem from three sources: dielectric polarization losses,
resistive losses in the plates and terminals, and skin-effect losses in the
leads and busbars at high frequencies. For this GE series, losses below 5 kHz
are less than 0.3 W/kVAR—amounting to approximately 90 W for a 300 kVAR unit.
While the absolute value may seem small, the heat is concentrated within a very
tiny volume inside the dielectric winding. The resulting heat flux density is so
high that natural cooling is insufficient to dissipate the heat; therefore,
water cooling is mandatory.
(V) Heat Transfer Path in Water-Cooled Designs
Each capacitor contains internal copper cooling tubes. Cooling water flows
directly through the areas where heat generation is most concentrated, carrying
away heat from dielectric and copper losses, which is then dissipated via an
external heat exchanger or cooling tower. The high thermal conductivity of
copper, combined with thin tube walls, ensures a minimal temperature gradient
between the tube wall and the dielectric material—a key factor enabling these
water-cooled units to achieve high power density in a compact form factor.
(VI) Capacitance Adjustment via Taps
The four 25 µF taps effectively divide the total capacitance into several
discrete, combinable units. In engineering applications, the total capacitance
can be adjusted by changing the number of connected units. This allows for
fine-tuning the resonant frequency and compensating for variations in the
induction coil—such as those occurring when a furnace body or crucible is
replaced. Furthermore, it enables the total current (reaching hundreds of
amperes) to be distributed across multiple terminals, thereby reducing the
temperature rise at any individual terminal.
II. Key Advantages
(I) High Power Density and Compact Footprint. By utilizing water cooling
instead of air cooling, the volume and weight for a given capacity are
significantly reduced. This facilitates dense arrangement within electrical
cabinets, shortens busbar lengths, and minimizes circuit inductance.
(II) Low Losses and High Efficiency. With a dielectric loss of less than
0.3 W/kVAR at frequencies below 5 kHz, a 300 kVAR unit generates only about 90 W
of heat. This results in lower electricity costs during long-term operation and
places a minimal burden on cooling systems.
(III) Dielectric Structure Capable of Withstanding High Ripple Currents.
This model is impregnated with "Dielektrol VIIa" insulating fluid. According to
GE’s product specifications, this fluid is paired with a "film-foil" dielectric
structure—consisting of metal foil electrodes and polypropylene film—which can
withstand significant ripple and surge currents. It is well-suited for
applications with highly fluctuating loads, such as melting or induction heating
(for forging/forming). (Please refer to the nameplate and accompanying technical
documentation for the specific dielectric structure of your unit.)
(IV) Long Design Lifespan. GE specifies a nominal service life of 20 years.
High batch consistency is ensured through processes such as winding in a
cleanroom environment, controlled fluid impregnation, and 100% electrical and
leakage testing.
(V) Four-Tap Configuration for Flexible Wiring. Depending on the power
supply voltage, furnace parameters, and power distribution requirements, units
can be connected in parallel or in groups. This allows for fine-tuning of total
capacitance and facilitates current balancing when multiple units are connected
in parallel within a cabinet.
(VI) Ample Current-Carrying Capacity of Terminals. The tinned copper
terminals are capable of carrying an RMS current of 300 A on a continuous basis.
Given the total current of approximately 754 A for this model, the load is
distributed across four sets of taps—resulting in about 188 A per set—which
provides a substantial safety margin.
(VII) Environmental Compliance. The insulating fluid is PCB-free and can be
disposed of via incineration or through hazardous waste management channels, in
full compliance with current environmental regulations. As the fluid is
classified as a Class IIIB combustible liquid, fire protection measures and
appropriate containment must be considered for the installation site.
.jpg)
(VIII) Industry Expertise. GE has been supplying water-cooled and
air-cooled capacitors to the induction heating and melting industry for over
fifty years. Its product portfolio spans ratings up to 4000 V, 50 kHz, and 4800
A, backed by extensive experience in providing integrated solutions.
III. Applications in Various Induction Heating Sectors
(I) Medium-Frequency Induction Melting (Cast Steel, Cast Iron, Copper
Alloys, Aluminum Alloys, Precious Metals)
Mechanism: A capacitor bank and the furnace’s induction coil form a
parallel resonant circuit, supplying the reactive power required to establish an
alternating magnetic field within the furnace. Industrial Value: The power
factor is improved from 0.3–0.5 to nearly 1.0, allowing power supply capacity to
be configured based on active power. This results in shorter melting times and
reduced electricity consumption per ton. Furthermore, the high circulating
current within the resonant circuit generates strong electromagnetic stirring,
ensuring greater uniformity in both composition and temperature.
(II) Induction Through-Heating and Forging Heating (Bars, Billets, Tube
Blanks)
Mechanism: The resonant circuit maintains a stable resonance point on
continuous production lines, enabling workpieces to reach forging temperatures
within seconds to tens of seconds. Industrial Value: Provides consistent heating
cycles, minimizes scale formation, and lowers energy consumption. The capacity
of the capacitor bank directly determines the upper limit of the power supply
that can be utilized.
(III) Induction Hardening and Heat Treatment (Gears, Shafts, Guide Rails,
Molds)
Mechanism: The resonant circuit ensures constant output power, allowing for
repeatable heating-depth profiles and temperature curves. Industrial Value:
Produces uniform hardened layers with minimal deformation and low scrap rates.
Multi-tap capacitor configurations facilitate precise adjustments to power and
frequency to meet specific process requirements.
(IV) Induction Brazing, Welding, and Sintering
Mechanism: Concentrates high power within a small volume, enabling rapid,
localized heating without compromising the properties of the base material.
Industrial Value: Ensures consistent welding quality for cutting tools, pipe
fittings, cemented carbides, and diamond tools, while keeping the heat-affected
zone (HAZ) to a minimum. (V) Vacuum Melting, Precision Casting, and Crystal
Growth
Mechanism: Capacitors with low loss and low outgassing provide stable
resonant reactive power within vacuum or protective atmosphere environments.
Industrial Value: Ensures steady power output, prevents frequency drift caused
by temperature-dependent capacitance variations, and maintains compositional
consistency in crystals and alloys.
(VI) Pipeline Coating, Shrink-Fitting, Annealing, and Continuous Production
Lines
Mechanism: Forms a tunable resonant circuit in conjunction with an
induction coil, accommodating variations in pipe diameter and wall thickness.
Industrial Value: Enables uniform curing of coatings, allows for adjustable
production speeds, and offers high overall electrical efficiency.
IV. Operational Procedures
(I) Pre-installation Inspection upon Arrival
Verify that the capacity, voltage, and frequency specified on the nameplate
match the order requirements and actual operating conditions. Inspect the
enclosure for any visible dents, bulges, or leaks, and check the bushings for
cracks or looseness. While minor dents do not affect performance, units with
extensive denting, fluid leakage, or damaged bushings must not be installed. Use
a megohmmeter (megger) to measure the insulation resistance between the
terminals and the enclosure, and record the ambient temperature and
humidity.
(II) Mechanical Installation
Multiple units should ideally be installed side-by-side on a sturdy support
frame, with the bushings oriented upward whenever possible. If an alternative
orientation is required, the support structure must be capable of securely
bearing the full weight of the unit. Supports must provide an adequate contact
surface; clamping the wide sides of the enclosure is strictly prohibited, as
this could lead to excessive internal pressure when the insulating fluid expands
due to heat. For units equipped with support brackets, lifting must be performed
by applying force to the brackets on both sides simultaneously. Never lift a
unit by its bushings or cooling pipe connections, and ensure that the cooling
pipes are not subjected to stress that could cause them to bend.
.jpg)
(III) Water
Circuit Connections
Both the water inlet and outlet pipes must be made of insulating flexible
material (such as rubber hose) and routed entirely within the electrical
enclosure. This prevents any metallic connection between the energized housing
and external water piping. Interconnecting pipes between capacitors must also be
insulated if a potential difference exists between their respective housings.
Water pipes should be grounded and bonded to the metal enclosure to ensure
equipotentiality. Before final connection, flush the piping system to ensure it
is free of debris, such as welding slag or fragments of sealant.
(IV) Electrical Connections
Follow the manufacturer’s wiring diagram precisely. Ensure sufficient
clearance for busbar hole spacing to avoid applying mechanical stress to the
terminals. Heavy busbars must be supported by insulators; they must not rely
solely on the capacitor terminals for structural support. Busbars should be
water-cooled or have a sufficiently large cross-sectional area to ensure their
temperature does not exceed 75°C. Apply an anti-oxidation compound at the
interface between aluminum conductors and copper terminals. The tightening
torque for terminals must not exceed 15 ft-lb (approx. 20 N·m); excessive torque
can damage gaskets or strip threads.
(V) Commissioning Procedure
Step 1: Start the cooling water system. Verify that the flow rate and
pressure are within specifications, purge all air from the piping, and check the
flow indicator or flow switch signal. Step 2: Confirm that the water outlet path
is clear before energizing the unit; energizing the system without active water
flow is strictly prohibited. Step 3: Gradually increase the load, starting from
a low power level. Monitor the current, voltage, outlet water temperature, and
operating noise at each stage. Step 4: During continuous operation at the rated
voltage and frequency, the outlet water temperature should remain stable below
45°C. Step 5: Once operation has stabilized, record baseline data—including
current for each bank, outlet water temperature, and pressure drop—to serve as a
reference for future trend analysis. (VI) Shutdown and Long-term
Decommissioning
To shut down the equipment, first reduce the power, then cut off the power
supply. Continue circulating the cooling water for 5–10 minutes after power-off
to allow internal heat to dissipate before stopping the water flow. After
cutting off the power, you must verify the absence of voltage, discharge the
unit, and short-circuit and ground the terminals before touching them. If the
equipment is to be decommissioned for a long period in an environment where
temperatures may fall below the freezing point, use compressed air to blow all
water out of the cooling pipes to prevent the copper tubes from freezing and
cracking. Before putting the equipment back into service, measure the insulation
resistance and check the integrity of all seals.
V. Precautions
(I) Never energize the equipment without cooling water or when the water
flow is insufficient. An interruption in cooling water can cause localized
overheating of the dielectric within minutes; this is the primary cause of
premature failure in water-cooled capacitors. It is recommended to install a
flow indicator equipped with electrical contacts on each cooling water branch,
connected to an alarm or trip circuit.
(II) Do not operate the equipment beyond the voltage, frequency, or
capacity specified on the nameplate. For high-frequency units (such as those
rated for 3 kHz), the voltage, frequency, and kVAR values listed on the
nameplate are the absolute maximum allowable limits; unlike low-frequency units,
there is no margin for overvoltage. GE explicitly states that only low-frequency
units (60–540 Hz) allow for a +10% overvoltage margin and a total kVAR capacity
of up to 135% of the rated value; this provision does not apply to the model in
question.
(III) Be cautious of tank circuit voltage and residual charge. Under
resonant conditions, the voltage across the capacitor may exceed the voltage of
the power supply busbar; therefore, actual measured tank circuit voltage must be
used as the reference during selection and commissioning. Some induction heating
capacitors do not include internal discharge resistors. This specific model is
not equipped with a pressure switch or mounting bracket; verify the discharge
method before putting it into operation. If there is no internal resistor, an
external discharge resistor must be added. The resistance value (in Ω) must not
be lower than the maximum potential charging voltage (in V). After discharge,
the terminals must be short-circuited and grounded. (IV) Control of Harmonics
and Switching Transients. Harmonic currents from the inverter cause additional
losses and temperature rise within the capacitor; if harmonic content is high,
calculations should be re-evaluated based on the actual RMS current. Thermal
cycling resulting from frequent switching accelerates the aging of the
dielectric material; therefore, unnecessary switching operations should be
minimized.
(V) Water Quality Determines Lifespan. Cooling water must be free of
impurities that could react with copper or form deposits; otherwise, the
lifespan of the capacitor will be limited to that of the cooling pipes. Industry
standards generally require the use of deionized water with a conductivity below
10 µS/cm (ideally below 2 µS/cm), a pH value between 6.5 and 8.0, low chloride
ion content, and a resistivity of at least 2500 Ω·cm. Poor water quality can
lead to electrolytic corrosion of copper pipes, perforation-induced leaks, and
increased leakage current.
(VI) Flow Rate and Pressure Must Remain Within Specified Ranges. The flow
rate for each capacitor should be between 1.0 GPM (approx. 3.8 L/min) and 2.5
GPM (approx. 9.5 L/min), with higher values recommended for high-capacity
units or units connected in series. Water supply pressure can reach up to 150
psi (approx. 1.0 MPa). Insufficient flow leads to inadequate heat dissipation,
while excessive flow can cause erosion of the copper pipes due to high velocity.
When cooling pipes are connected in series, the supply pressure must be
sufficient to maintain the required flow rate.
(VII) Grounding and Leakage Protection Are Mandatory. The enclosure must be
reliably grounded, and both the water inlet/outlet pipes and the electrical
cabinet must be equipotentially bonded. Cooling water may conduct leakage
current when at a high potential; the length of insulating hoses should be
determined based on the water's resistivity and the allowable leakage
current—though it should be noted that insulating hoses cannot serve as a
substitute for proper grounding.
(VIII) Handling of Failed Units. If a capacitor casing shows signs of
bulging, leakage, or emits abnormal sounds, immediately disconnect the power,
discharge the unit, and short-circuit the terminals to the ground. Allow the
unit to cool down completely before moving it to prevent the pressurized casing
from rupturing and spraying its liquid contents. If the insulating liquid comes
into contact with your skin, wash the area thoroughly with soap and water; if it
enters your eyes, flush them with copious amounts of water and seek medical
attention. When replacing a faulty unit, consult the equipment manufacturer to
verify the correct fuse and protection settings to prevent a recurrence of the
fault upon re-energization.
(IX) Environment, Fire Safety, and Disposal. Capacitors must be installed
within an enclosure capable of containing a potential fire, kept away from
flammable materials, and either surrounded by a protective barrier or mounted at
an elevated location. The insulating liquid is classified as a Class IIIB
combustible liquid; there is a risk of combustion if an electric arc punctures
the casing. Discarded units must be handled through authorized hazardous waste
disposal channels. The preferred disposal method involves incinerating the
liquid components and sending the solid parts to a designated hazardous waste
facility; unauthorized dismantling or dumping is strictly prohibited.
VI. Frequently Asked Questions (FAQ)
Q1: Can the 19L0638WH1 model be used in a 50 Hz power-frequency system?
A1: No. This model is designed for 3000 Hz operation; its dielectric
thickness, terminal configuration, and cooling structure are all optimized for
high-frequency conditions. While the unit will still provide capacitance at
power frequency, its reactive power output would only be approximately 5 kVAR.
Furthermore, low-frequency applications impose entirely different requirements
on the dielectric and terminals, necessitating the selection of a different
model.
Q2: What should the outlet water temperature be?
A2: During continuous operation at rated voltage and frequency, the outlet
water temperature must not exceed 45°C. If the temperature consistently exceeds
this limit despite normal water flow, it indicates insufficient flow, an
excessively high inlet water temperature, or abnormal harmonic losses; the unit
should be shut down for inspection. Q3: What is the appropriate cooling water
flow rate?
A: For a single unit, the flow rate should be between 3.8 and 9.5 L/min.
For a 300 kVAR high-capacity unit, a flow rate of 2.0–2.5 GPM (approximately
7.6–9.5 L/min) is recommended, along with the implementation of flow
monitoring.
Q4: Why is water quality emphasized more than flow rate?
A: Insufficient flow leads to short-term overheating, whereas poor water
quality causes long-term electrolytic corrosion. If a copper tube develops a
perforation, water can enter the dielectric zone, leading to immediate
electrical breakdown—a failure that is typically irreparable. Therefore, water
quality is the decisive factor for the unit's service life.
Q5: Can this unit be directly replaced by a capacitor of the same capacity
from another brand?
A: You must verify several parameters: capacitance, rated voltage, rated
frequency, rated current, tap configuration, mounting dimensions, water
connection interfaces, and cooling flow requirements. Matching the capacity
alone is insufficient; the resonant frequency and the tank circuit voltage are
the critical constraints.
VII. Conclusion
The value of the 19L0638WH1 lies not merely in its "300 kVAR" rating, but
in its integration of high-capacity reactive power, low-loss dielectric
materials, and efficient water cooling into a single, compact unit. This enables
induction heating systems to operate with a power factor approaching 1, while
delivering hundreds of amperes of resonant circulating current to the induction
coil in a stable and controlled manner. Selecting the correct model is only the
starting point; factors such as water quality, flow rate, outlet water
temperature, terminal torque, and proper discharge grounding are all critical
details that determine whether the capacitor will actually achieve its 20-year
design lifespan.