510Processor Operating
TEMPERATURE
10° to 35°C (50° to 95°F) at sea level with an altitude derating of 1.0°C per every 305 m (1.8°F per every 1000 ft) above sea level to a maximum of 3050 m (10,000 ft); no direct sustained sunlight. Maximum rate of change is 10°C/hr (18°F/hr). The upper limit may be limited by the type and number of options installed.
System performance may be reduced if operating with a fan fault or above 30°C (86°F).
Note:10 to 40°C (50 to 104°F) with the Optional P0928NE HP DL380 Gen 9 High Performance Fan Option kit Foxboro Part number P0928NE
RELATIVE HUMIDITY
10% to 90% relative humidity (Rh), 28°C (82.4°F) maximum wet bulb temperature, non-condensing
MAXIMUM VIBRATION
0.26 G at 5 to 350 Hz in operational orientations
SHOCK
Half sine shock in all operational orientations of 31 G +/-5% with a pulse duration of 2.6 ms
+/-10%
ALTITUDE
3050 m (10,000 ft). This value may be limited by the type and number of options installed.
Maximum allowable altitude change rate is 457 m/min (1500 ft/min).
Processor Storage
TEMPERATURE
-30° to 60°C (-22° to 140°F). Maximum rate of change is 20°C/hr (36°F/hr).
RELATIVE HUMIDITY 5% to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb temperature, noncondensing
MAXIMUM VIBRATION
1.54 G rms at 10 Hz to 250 Hz in all orientations
SHOCK
Half sine shock on all six sides of 71 G +/-5%
with a pulse duration of 2 ms +/-10%. Square
wave shock on all six sides of 27 G with velocity
change @ 235 in/sec. or greater.
ALTITUDE
-16 to 10,600 m (-50 ft to 35,000 ft)
Processor Environmental
LOCATION
UL/UL-C listed as suitable for use in ordinary locations and meets ordinary safety standards for fire and shock hazards.
CONTAMINATION
Class G1 (Mild) as defined in ISA Standard S71.04