19L0052WH1 Water-Cooled Induction Heating Capacitor GE-19L0052WH1

Each capacitor unit contains internal copper cooling tubes. Cooling water flows directly through the areas where heat generation is most concentrated, carrying away heat produced by dielectric and copper losses, which is then dissipated via an external heat exchanger or cooling tower. The high thermal conductivity of copper, combined with the thin walls of the cooling tubes, minimizes the temperature gradient between the tube walls and the dielectric medium—a key factor that enables these water-cooled units to achieve high power density within a compact footprint. During each cycle, energy oscillates between the electric field of the capacitor and the magnetic field of the induction coil. In essence, the capacitor functions as a "reactive power transit station": it supplies the necessary reactive power directly to the induction coil, preventing this power from having to travel back and forth between the power source and the load. This reduces the required capacity of the power source and minimizes line losses.

Product Application Label
Product Brand Tag
  • Description
  • Reviews

  All products listed on this website are specialized items; their market prices are subject to frequent fluctuations.

  Please rely on the quotes provided by our customer service team. As these are new products, the prices displayed may not be final or accurate.

  Before placing an order, please consult with our customer service representatives to confirm the specific model, product details, and current pricing. We offer both used and new equipment; please contact us to discuss your requirements.


  I. Operating Principle

  (I) Generation of Reactive Power

  The charge between the plates of a capacitor undergoes repeated charging and discharging cycles in response to the polarity of an alternating voltage. This causes the current phase to lead the voltage by approximately 90°, manifesting as capacitive reactive power within the circuit. The reactive power (Q) is directly proportional to the frequency (f), capacitance (C), and the square of the voltage (U): Q = 2πfCU². This explains why the capacity of the same capacitor can vary drastically at different frequencies—for instance, a 100 µF capacitor yields approximately 5 kVAR at 400 V and 50 Hz, but reaches 300 kVAR at 3 kHz. This is precisely why capacitors used for induction heating must be purpose-designed.

  (II) Formation of a Parallel Resonant Tank Circuit with the Induction Coil

  A capacitor bank (C) connected in parallel with an induction coil (L) forms a parallel resonant tank circuit, with a resonant frequency of f₀ = 1/(2π√(LC)). At the point of resonance, the inductive current and capacitive current cancel each other out; the power supply only needs to compensate for the active power losses within the tank circuit, resulting in a power factor close to 1. Taking L ≈ 20 µH and C ≈ 100 µF as an example, the resonant frequency is approximately 3.6 kHz, and the characteristic impedance is about 0.45 Ω—a value roughly equivalent to the capacitive reactance of the capacitor at the resonant frequency. At this stage, the circulating current within the resonant circuit can reach several times the magnitude of the power supply's output current. It is precisely this circulating current that establishes a strong alternating magnetic field within the induction coil—a field sufficiently intense to melt metal.

  (III) Energy Exchange Between Electric and Magnetic Fields

  Within each cycle, energy oscillates between the electric field of the capacitor and the magnetic field of the induction coil. In effect, the capacitor functions as a "reactive power relay station": it supplies the necessary reactive power locally to the induction coil, preventing this power from having to travel back and forth between the power supply and the load. This reduces the required capacity of the power supply and minimizes line losses.

  (IV) Losses and Heat Generation

  Operating losses stem from three sources: dielectric polarization losses, resistive losses in the plates and terminals, and skin-effect losses in the leads and busbars at high frequencies. For this GE series, losses below 5 kHz are less than 0.3 W/kVAR—amounting to approximately 90 W for a 300 kVAR unit. While the absolute value may seem small, the heat is concentrated within a very tiny volume inside the dielectric winding. The resulting heat flux density is so high that natural cooling is insufficient to dissipate the heat; therefore, water cooling is mandatory.

  (V) Heat Transfer Path in Water-Cooled Designs

  Each capacitor contains internal copper cooling tubes. Cooling water flows directly through the areas where heat generation is most concentrated, carrying away heat from dielectric and copper losses, which is then dissipated via an external heat exchanger or cooling tower. The high thermal conductivity of copper, combined with thin tube walls, ensures a minimal temperature gradient between the tube wall and the dielectric material—a key factor enabling these water-cooled units to achieve high power density in a compact form factor.

  (VI) Capacitance Adjustment via Taps

  The four 25 µF taps effectively divide the total capacitance into several discrete, combinable units. In engineering applications, the total capacitance can be adjusted by changing the number of connected units. This allows for fine-tuning the resonant frequency and compensating for variations in the induction coil—such as those occurring when a furnace body or crucible is replaced. Furthermore, it enables the total current (reaching hundreds of amperes) to be distributed across multiple terminals, thereby reducing the temperature rise at any individual terminal.


  II. Key Advantages

  (I) High Power Density and Compact Footprint. By utilizing water cooling instead of air cooling, the volume and weight for a given capacity are significantly reduced. This facilitates dense arrangement within electrical cabinets, shortens busbar lengths, and minimizes circuit inductance.

  (II) Low Losses and High Efficiency. With a dielectric loss of less than 0.3 W/kVAR at frequencies below 5 kHz, a 300 kVAR unit generates only about 90 W of heat. This results in lower electricity costs during long-term operation and places a minimal burden on cooling systems.

  (III) Dielectric Structure Capable of Withstanding High Ripple Currents. This model is impregnated with "Dielektrol VIIa" insulating fluid. According to GE’s product specifications, this fluid is paired with a "film-foil" dielectric structure—consisting of metal foil electrodes and polypropylene film—which can withstand significant ripple and surge currents. It is well-suited for applications with highly fluctuating loads, such as melting or induction heating (for forging/forming). (Please refer to the nameplate and accompanying technical documentation for the specific dielectric structure of your unit.)

  (IV) Long Design Lifespan. GE specifies a nominal service life of 20 years. High batch consistency is ensured through processes such as winding in a cleanroom environment, controlled fluid impregnation, and 100% electrical and leakage testing.

  (V) Four-Tap Configuration for Flexible Wiring. Depending on the power supply voltage, furnace parameters, and power distribution requirements, units can be connected in parallel or in groups. This allows for fine-tuning of total capacitance and facilitates current balancing when multiple units are connected in parallel within a cabinet.

  (VI) Ample Current-Carrying Capacity of Terminals. The tinned copper terminals are capable of carrying an RMS current of 300 A on a continuous basis. Given the total current of approximately 754 A for this model, the load is distributed across four sets of taps—resulting in about 188 A per set—which provides a substantial safety margin.

  (VII) Environmental Compliance. The insulating fluid is PCB-free and can be disposed of via incineration or through hazardous waste management channels, in full compliance with current environmental regulations. As the fluid is classified as a Class IIIB combustible liquid, fire protection measures and appropriate containment must be considered for the installation site.

  (VIII) Industry Expertise. GE has been supplying water-cooled and air-cooled capacitors to the induction heating and melting industry for over fifty years. Its product portfolio spans ratings up to 4000 V, 50 kHz, and 4800 A, backed by extensive experience in providing integrated solutions.


  III. Applications in Various Induction Heating Sectors

  (I) Medium-Frequency Induction Melting (Cast Steel, Cast Iron, Copper Alloys, Aluminum Alloys, Precious Metals)

  Mechanism: A capacitor bank and the furnace’s induction coil form a parallel resonant circuit, supplying the reactive power required to establish an alternating magnetic field within the furnace. Industrial Value: The power factor is improved from 0.3–0.5 to nearly 1.0, allowing power supply capacity to be configured based on active power. This results in shorter melting times and reduced electricity consumption per ton. Furthermore, the high circulating current within the resonant circuit generates strong electromagnetic stirring, ensuring greater uniformity in both composition and temperature.

  (II) Induction Through-Heating and Forging Heating (Bars, Billets, Tube Blanks)

  Mechanism: The resonant circuit maintains a stable resonance point on continuous production lines, enabling workpieces to reach forging temperatures within seconds to tens of seconds. Industrial Value: Provides consistent heating cycles, minimizes scale formation, and lowers energy consumption. The capacity of the capacitor bank directly determines the upper limit of the power supply that can be utilized.

  (III) Induction Hardening and Heat Treatment (Gears, Shafts, Guide Rails, Molds)

  Mechanism: The resonant circuit ensures constant output power, allowing for repeatable heating-depth profiles and temperature curves. Industrial Value: Produces uniform hardened layers with minimal deformation and low scrap rates. Multi-tap capacitor configurations facilitate precise adjustments to power and frequency to meet specific process requirements.

  (IV) Induction Brazing, Welding, and Sintering

  Mechanism: Concentrates high power within a small volume, enabling rapid, localized heating without compromising the properties of the base material. Industrial Value: Ensures consistent welding quality for cutting tools, pipe fittings, cemented carbides, and diamond tools, while keeping the heat-affected zone (HAZ) to a minimum. (V) Vacuum Melting, Precision Casting, and Crystal Growth

  Mechanism: Capacitors with low loss and low outgassing provide stable resonant reactive power within vacuum or protective atmosphere environments. Industrial Value: Ensures steady power output, prevents frequency drift caused by temperature-dependent capacitance variations, and maintains compositional consistency in crystals and alloys.

  (VI) Pipeline Coating, Shrink-Fitting, Annealing, and Continuous Production Lines

  Mechanism: Forms a tunable resonant circuit in conjunction with an induction coil, accommodating variations in pipe diameter and wall thickness. Industrial Value: Enables uniform curing of coatings, allows for adjustable production speeds, and offers high overall electrical efficiency.


  IV. Operational Procedures

  (I) Pre-installation Inspection upon Arrival

  Verify that the capacity, voltage, and frequency specified on the nameplate match the order requirements and actual operating conditions. Inspect the enclosure for any visible dents, bulges, or leaks, and check the bushings for cracks or looseness. While minor dents do not affect performance, units with extensive denting, fluid leakage, or damaged bushings must not be installed. Use a megohmmeter (megger) to measure the insulation resistance between the terminals and the enclosure, and record the ambient temperature and humidity.

  (II) Mechanical Installation

  Multiple units should ideally be installed side-by-side on a sturdy support frame, with the bushings oriented upward whenever possible. If an alternative orientation is required, the support structure must be capable of securely bearing the full weight of the unit. Supports must provide an adequate contact surface; clamping the wide sides of the enclosure is strictly prohibited, as this could lead to excessive internal pressure when the insulating fluid expands due to heat. For units equipped with support brackets, lifting must be performed by applying force to the brackets on both sides simultaneously. Never lift a unit by its bushings or cooling pipe connections, and ensure that the cooling pipes are not subjected to stress that could cause them to bend.


       (III) Water Circuit Connections

  Both the water inlet and outlet pipes must be made of insulating flexible material (such as rubber hose) and routed entirely within the electrical enclosure. This prevents any metallic connection between the energized housing and external water piping. Interconnecting pipes between capacitors must also be insulated if a potential difference exists between their respective housings. Water pipes should be grounded and bonded to the metal enclosure to ensure equipotentiality. Before final connection, flush the piping system to ensure it is free of debris, such as welding slag or fragments of sealant.

  (IV) Electrical Connections

  Follow the manufacturer’s wiring diagram precisely. Ensure sufficient clearance for busbar hole spacing to avoid applying mechanical stress to the terminals. Heavy busbars must be supported by insulators; they must not rely solely on the capacitor terminals for structural support. Busbars should be water-cooled or have a sufficiently large cross-sectional area to ensure their temperature does not exceed 75°C. Apply an anti-oxidation compound at the interface between aluminum conductors and copper terminals. The tightening torque for terminals must not exceed 15 ft-lb (approx. 20 N·m); excessive torque can damage gaskets or strip threads.

  (V) Commissioning Procedure

  Step 1: Start the cooling water system. Verify that the flow rate and pressure are within specifications, purge all air from the piping, and check the flow indicator or flow switch signal. Step 2: Confirm that the water outlet path is clear before energizing the unit; energizing the system without active water flow is strictly prohibited. Step 3: Gradually increase the load, starting from a low power level. Monitor the current, voltage, outlet water temperature, and operating noise at each stage. Step 4: During continuous operation at the rated voltage and frequency, the outlet water temperature should remain stable below 45°C. Step 5: Once operation has stabilized, record baseline data—including current for each bank, outlet water temperature, and pressure drop—to serve as a reference for future trend analysis. (VI) Shutdown and Long-term Decommissioning

  To shut down the equipment, first reduce the power, then cut off the power supply. Continue circulating the cooling water for 5–10 minutes after power-off to allow internal heat to dissipate before stopping the water flow. After cutting off the power, you must verify the absence of voltage, discharge the unit, and short-circuit and ground the terminals before touching them. If the equipment is to be decommissioned for a long period in an environment where temperatures may fall below the freezing point, use compressed air to blow all water out of the cooling pipes to prevent the copper tubes from freezing and cracking. Before putting the equipment back into service, measure the insulation resistance and check the integrity of all seals.


  V. Precautions

  (I) Never energize the equipment without cooling water or when the water flow is insufficient. An interruption in cooling water can cause localized overheating of the dielectric within minutes; this is the primary cause of premature failure in water-cooled capacitors. It is recommended to install a flow indicator equipped with electrical contacts on each cooling water branch, connected to an alarm or trip circuit.

  (II) Do not operate the equipment beyond the voltage, frequency, or capacity specified on the nameplate. For high-frequency units (such as those rated for 3 kHz), the voltage, frequency, and kVAR values listed on the nameplate are the absolute maximum allowable limits; unlike low-frequency units, there is no margin for overvoltage. GE explicitly states that only low-frequency units (60–540 Hz) allow for a +10% overvoltage margin and a total kVAR capacity of up to 135% of the rated value; this provision does not apply to the model in question.

  (III) Be cautious of tank circuit voltage and residual charge. Under resonant conditions, the voltage across the capacitor may exceed the voltage of the power supply busbar; therefore, actual measured tank circuit voltage must be used as the reference during selection and commissioning. Some induction heating capacitors do not include internal discharge resistors. This specific model is not equipped with a pressure switch or mounting bracket; verify the discharge method before putting it into operation. If there is no internal resistor, an external discharge resistor must be added. The resistance value (in Ω) must not be lower than the maximum potential charging voltage (in V). After discharge, the terminals must be short-circuited and grounded. (IV) Control of Harmonics and Switching Transients. Harmonic currents from the inverter cause additional losses and temperature rise within the capacitor; if harmonic content is high, calculations should be re-evaluated based on the actual RMS current. Thermal cycling resulting from frequent switching accelerates the aging of the dielectric material; therefore, unnecessary switching operations should be minimized.

  (V) Water Quality Determines Lifespan. Cooling water must be free of impurities that could react with copper or form deposits; otherwise, the lifespan of the capacitor will be limited to that of the cooling pipes. Industry standards generally require the use of deionized water with a conductivity below 10 µS/cm (ideally below 2 µS/cm), a pH value between 6.5 and 8.0, low chloride ion content, and a resistivity of at least 2500 Ω·cm. Poor water quality can lead to electrolytic corrosion of copper pipes, perforation-induced leaks, and increased leakage current.

  (VI) Flow Rate and Pressure Must Remain Within Specified Ranges. The flow rate for each capacitor should be between 1.0 GPM (approx. 3.8 L/min) and 2.5 GPM (approx. 9.5 L/min), with higher values recommended for high-capacity units or units connected in series. Water supply pressure can reach up to 150 psi (approx. 1.0 MPa). Insufficient flow leads to inadequate heat dissipation, while excessive flow can cause erosion of the copper pipes due to high velocity. When cooling pipes are connected in series, the supply pressure must be sufficient to maintain the required flow rate.

  (VII) Grounding and Leakage Protection Are Mandatory. The enclosure must be reliably grounded, and both the water inlet/outlet pipes and the electrical cabinet must be equipotentially bonded. Cooling water may conduct leakage current when at a high potential; the length of insulating hoses should be determined based on the water's resistivity and the allowable leakage current—though it should be noted that insulating hoses cannot serve as a substitute for proper grounding.

  (VIII) Handling of Failed Units. If a capacitor casing shows signs of bulging, leakage, or emits abnormal sounds, immediately disconnect the power, discharge the unit, and short-circuit the terminals to the ground. Allow the unit to cool down completely before moving it to prevent the pressurized casing from rupturing and spraying its liquid contents. If the insulating liquid comes into contact with your skin, wash the area thoroughly with soap and water; if it enters your eyes, flush them with copious amounts of water and seek medical attention. When replacing a faulty unit, consult the equipment manufacturer to verify the correct fuse and protection settings to prevent a recurrence of the fault upon re-energization.

  (IX) Environment, Fire Safety, and Disposal. Capacitors must be installed within an enclosure capable of containing a potential fire, kept away from flammable materials, and either surrounded by a protective barrier or mounted at an elevated location. The insulating liquid is classified as a Class IIIB combustible liquid; there is a risk of combustion if an electric arc punctures the casing. Discarded units must be handled through authorized hazardous waste disposal channels. The preferred disposal method involves incinerating the liquid components and sending the solid parts to a designated hazardous waste facility; unauthorized dismantling or dumping is strictly prohibited.


  VI. Frequently Asked Questions (FAQ)

  Q1: Can the 19L0052WH1 model be used in a 50 Hz power-frequency system?

  A1: No. This model is designed for 3000 Hz operation; its dielectric thickness, terminal configuration, and cooling structure are all optimized for high-frequency conditions. While the unit will still provide capacitance at power frequency, its reactive power output would only be approximately 5 kVAR. Furthermore, low-frequency applications impose entirely different requirements on the dielectric and terminals, necessitating the selection of a different model.

  Q2: What should the outlet water temperature be?

  A2: During continuous operation at rated voltage and frequency, the outlet water temperature must not exceed 45°C. If the temperature consistently exceeds this limit despite normal water flow, it indicates insufficient flow, an excessively high inlet water temperature, or abnormal harmonic losses; the unit should be shut down for inspection. Q3: What is the appropriate cooling water flow rate?

  A: For a single unit, the flow rate should be between 3.8 and 9.5 L/min. For a 300 kVAR high-capacity unit, a flow rate of 2.0–2.5 GPM (approximately 7.6–9.5 L/min) is recommended, along with the implementation of flow monitoring.

  Q4: Why is water quality emphasized more than flow rate?

  A: Insufficient flow leads to short-term overheating, whereas poor water quality causes long-term electrolytic corrosion. If a copper tube develops a perforation, water can enter the dielectric zone, leading to immediate electrical breakdown—a failure that is typically irreparable. Therefore, water quality is the decisive factor for the unit's service life.

  Q5: Can this unit be directly replaced by a capacitor of the same capacity from another brand?

  A: You must verify several parameters: capacitance, rated voltage, rated frequency, rated current, tap configuration, mounting dimensions, water connection interfaces, and cooling flow requirements. Matching the capacity alone is insufficient; the resonant frequency and the tank circuit voltage are the critical constraints.


  VII. Conclusion

  The value of the 19L0052WH1 lies not merely in its "300 kVAR" rating, but in its integration of high-capacity reactive power, low-loss dielectric materials, and efficient water cooling into a single, compact unit. This enables induction heating systems to operate with a power factor approaching 1, while delivering hundreds of amperes of resonant circulating current to the induction coil in a stable and controlled manner. Selecting the correct model is only the starting point; factors such as water quality, flow rate, outlet water temperature, terminal torque, and proper discharge grounding are all critical details that determine whether the capacitor will actually achieve its 20-year design lifespan.


Recommended products:
DS3820HSPB GE
151X1215GD01SA21 GE
151X1202YE04PP01 GE
151X1225DB02MP01 GE
151X1225DB01SA04 GE
151X207BA10SA01 GE
151X1230BS01WH05 GE
151X1225EK01PC03R GE
GE 151X1225DF01PC01
More......

1.Do you offer global shipping?

Yes. We have local distribution centers on every continent, enabling us to quickly ship parts to anywhere in the world.

2. What payment methods and currencies do you accept?

To make your purchasing process as simple and convenient as possible, we offer a variety of payment methods, including bank transfer, cheque, and PayPal. We also accept most major credit and debit cards, such as Visa, Mastercard, and American Express. We accept payments in most major global currencies, but we recommend using US Dollars (USD), British Pounds (GBP), or Euros (EUR). Using other currencies may incur additional fees. All transactions are securely processed by HSBC and HSBC Merchant Services.

3.How much parts do you currently have in stock?

We have a vast inventory of new, refurbished, and used automation components, including products from well-known manufacturers such as ABB and Schneider Electric. If you can't find the part you need, don't worry. We work closely with professional suppliers worldwide, and even if the part you need isn't listed on our website, we can provide you with a tailored quote.

4.Who should I contact if I encounter any problems?

Our experienced customer service team will handle any issues after you place your order.

Your email address will not be published. Required fields are marked *
Your rating*
Name*
Email*
Code*
Your review*
Save my name,email,and website in this browser for the next time|comment.
Recommended products
Our website uses cookies to ensure you have the best experience, you are agreeing to our use of cookies in accordance with our Cookie Policy.
Online Message
Online
Message
  • home
  • message
  • tel
  • Email
  • top