I. Working Principle
Signal Acquisition: The PT voltage transformer introduces the generator
voltage and the power grid system voltage. Simultaneously, it acquires feedback
from the turbine guide vane (gate) opening and circuit breaker position contact
signals, sending them to the board's analog and digital channels.
Comparison Calculation: The board's internal CPU calculates voltage
difference, frequency difference, and phase angle difference in real time and
compares them with the system's set grid connection allowable window.
Closed-Loop Regulation: Outputs regulation commands to the governor,
controlling the turbine guide vane gate opening, changing the unit speed and
voltage, and continuously reducing the frequency and phase angle
differences.
.gif)
Closing Output: When the frequency difference, voltage difference, and
phase angle are all within the allowable range, the internal relay outputs a
closing command, closing the generator circuit breaker to complete grid
connection.
Interlock Protection: For parameter exceeding limits or signal
disconnection, the closing circuit is double-interlocked by hardware and
software, prohibiting asynchronous grid connection. Simultaneously, a fault
alarm is output and reported to the upper control system via the VME bus.
Self-Diagnosis: The board continuously self-checks power supply, data
acquisition channels, and bus communication. An abnormality illuminates the
panel fault LED.
II. Core Functions:
Automatic Quasi-Synchronous Grid Connection: Fully automatic detection of
voltage, frequency, and phase; automatic adjustment of the unit; outputting a
circuit breaker closing command when conditions are met.
Turbine Guide Vane (Gate) Interlocking Control: Outputs control signals to
adjust the guide vane opening, coordinating grid connection and load connection.
This is the origin of the name "Gate Control Unit."
Synchronization Interlocking Protection: Directly blocks the closing output
in cases of excessive frequency difference, phase angle exceeding limits, or PT
disconnection, preventing asynchronous impacts from damaging the generator.
.jpg)
Local/Remote Mode Switching: Supports local manual synchronization
operation and also receives remote commands from the DCS/upper-level system.
Status Acquisition and Feedback: Collects circuit breaker open/close
positions and gate opening, uploading operating status and fault codes.
Hardware Self-Diagnosis: Power failure, channel damage, and bus
abnormalities trigger panel indicator lights and system alarm outputs.
III. Application Scenarios:
Hydropower Plants: Automatic grid connection of turbine generator units and
control of guide vane gates are the primary applications of this board.
Synchronization and Grid Connection Control of Small and Medium-Sized
Thermal Power Units and Gas Turbine Units:
Plant and Mining Self-Supplied Power Stations and Distributed Energy Power
Stations: Control of unit grid connection and disconnection from the public
grid. This card is used as a synchronization gate control card within the
control system rack of an older ABB VME architecture unit.
IV. Usage Precautions
Hardware Installation
This is a VME rack-mount card. Before inserting or removing it, the 24V
control power supply to the rack must be disconnected. Hot-swapping is
prohibited, as it will burn out the backplane interface of the card.
Ensure proper chassis cooling. Operating temperature: -20℃ to +60℃. Avoid
damp, dusty, and high-vibration environments for the rack.
Keep the gold fingers of the VME slot on the backplane clean. Poor contact
will result in communication loss and random fault reports.
Wiring and Signals
The PT voltage input circuit must use shielded cable, with the shield
grounded at one end. The high-voltage PT circuit and the 24V low-voltage circuit
should be routed separately to avoid interference and synchronization
errors.
Short circuits are strictly prohibited in the PT secondary circuit. After
wiring, verify the phase sequence. Incorrect phase sequence will directly lead
to grid connection failure.
The gate opening feedback and circuit breaker position dry contact wiring
must be secure; loose connections will cause synchronization logic
abnormalities.
Parameter Setting
Frequency difference, voltage difference, and phase angle closing window
parameters must be strictly set according to the unit's specifications. An
excessively large window setting will cause grid connection impact; an
excessively small window will result in closing failure.

After replacing spare parts, the internal configuration parameters of the
circuit board must be verified. The default parameters of new/removed circuit
boards may not be compatible with the field unit.
Fault Risk Warning
PT disconnection and wiring interference will cause missynchronization
risks; a simulated transmission test must be performed after maintenance; do not
directly connect to the grid with a real unit.
Recommended related products:
5SHX06F6004 3BHB003387R0101
5SHX10H6004 3BHB003230R0101
5SHX1445H0001 3BHL000391P0101
5SHX1445H0001 3BHL000391P0101
5SHX1445H0001 3BHB003230R0101
5SHX2645L0004 3BHB003154R0101
5SHY3545L0003 3BHB004692R001
5SHY3545L0005 3BHB004692R0001
5SHY3545L0009 3BHB013085R0001
5SHY3545L0010 3BHE009681R0101
3BHB009885R0005 S-093H
3BHB009885R5311 S-093R
3BHB012897R0003 S-053M
3BHB009885R0004 S-093H
3BHB009884R0021 S-073N
3BHB018008R0003 S-113H
S-093N 3BHB009885R0021
More......
1.Do you offer global shipping?
Yes. We have local distribution centers on every continent, enabling us to quickly ship parts to anywhere in the world.
2. What payment methods and currencies do you accept?
To make your purchasing process as simple and convenient as possible, we offer a variety of payment methods, including bank transfer, cheque, and PayPal. We also accept most major credit and debit cards, such as Visa, Mastercard, and American Express. We accept payments in most major global currencies, but we recommend using US Dollars (USD), British Pounds (GBP), or Euros (EUR). Using other currencies may incur additional fees. All transactions are securely processed by HSBC and HSBC Merchant Services.
3.How much parts do you currently have in stock?
We have a vast inventory of new, refurbished, and used automation components, including products from well-known manufacturers such as ABB and Schneider Electric. If you can't find the part you need, don't worry. We work closely with professional suppliers worldwide, and even if the part you need isn't listed on our website, we can provide you with a tailored quote.
4.Who should I contact if I encounter any problems?
Our experienced customer service team will handle any issues after you place your order.