3BHE020455R0103 Alternative Names:
Process Control Unit 3BHE020455R0103
3BHE020455R0103 Central Processing Unit
AC 800PEC Process Control System 3BHE020455R0103
I. Operating Principle
This CPU unit serves as the computational and logic core of the excitation
regulator; together with the data acquisition board, I/O board, and pulse
amplification board, it forms a complete excitation control system.
Signal Acquisition: Receives generator terminal voltage, stator current,
and rotor current signals from voltage and current transformers; simultaneously
acquires binary signals such as circuit breaker status, raise/lower excitation
commands, and protection contact status.
Closed-loop Regulation Calculation: Features built-in algorithms for AVR
(Automatic Voltage Regulator), FCR (Field Current Regulator), and PSS (Power
System Stabilizer). It compares the voltage setpoint with the actual terminal
voltage in real-time and outputs control signals via PID calculation.
Pulse Generation: Converts regulation calculation results into thyristor
trigger pulse commands and transmits them to the pulse board. This controls the
conduction angle of the thyristors within the excitation power cabinet, thereby
adjusting the generator rotor excitation current to achieve stable control of
the terminal voltage. Logic and Protection Processing: Integrates various
excitation system protection logics, including over-excitation,
under-excitation, V/Hz limiting, stator current limiting, rotor overcurrent, and
loss-of-field monitoring; simultaneously handles system status assessment,
switching between active and standby channels, fault alarming, and event
logging.
Communication and Interaction: Communicates via onboard interfaces with the
excitation system's HMI, DCS, and power plant monitoring systems; uploads data
such as excitation current, voltage, fault codes, and operating status, while
receiving remote control commands.

Dual-Channel Redundancy Mechanism: Typically used in dual-channel
excitation systems where two CPUs serve as backups for each other. When the
primary CPU operates normally, the standby CPU synchronously acquires all
signals and tracks the primary regulator's output; in the event of a primary CPU
failure, power anomaly, or sampling error, the system performs a bumpless
transfer to the standby channel, ensuring uninterrupted excitation
operation.
II. Usage Instructions
Hardware Installation: Install the board into a standard rack slot within
the excitation control cabinet and secure it firmly; ensure reliable connection
of the backplane bus connector; connect external sampling cables, discrete
signals, and communication cables to the corresponding terminals according to
the schematics, ensuring separate routing for high-voltage and low-voltage lines
to prevent interference.
Pre-power-up Checks: Verify the supply voltage and inspect the backplane
for short circuits or loose wiring; confirm that instrument transformer
secondary circuits are free of open circuits and properly grounded; verify that
DIP switch settings and hardware addresses are configured according to project
schematics.
Power-up and Startup: Apply auxiliary power first; upon power-up, the CPU
executes a self-test routine. The self-test covers memory, firmware, A/D
sampling circuits, bus communication, and board hardware. If the self-test
passes without anomalies, the system enters standby mode; if it fails, the
corresponding fault LED illuminates, and the fault event is logged. Parameter
Configuration: Connect to the CPU via the excitation HMI panel or host software
to input unit parameters: generator rated voltage, rated rotor current,
transformer ratios, PID parameters, limit curves, protection settings, PSS
parameters, communication addresses, and channel switching logic. Parameters are
downloaded to the CPU's flash memory for permanent storage.
Static Commissioning: With the unit stationary, apply simulated voltage and
current signals to verify sampling accuracy; test AVR regulation response, field
boosting/bucking, limiting functions, and protection logic; and verify the
dual-channel switching function.
Grid Connection and Operation: Before field flashing, set the CPU to
automatic AVR mode; during field flashing, the CPU automatically regulates
excitation to establish terminal voltage; after grid connection, maintain
constant terminal voltage and respond to system voltage fluctuations; switching
to manual FCR (rotor current regulation) mode is supported.
III. Operation Methods
1. Mode Switching
Automatic AVR Mode: Default operating mode, regulating based on terminal
voltage. Switching can be performed via the local panel or remotely via DCS.
Manual FCR Mode: Regulates based on rotor current; generally used for
testing or fault conditions; long-term grid-connected operation in this mode is
not recommended.
Channel Switching: Supports automatic fault-based switching as well as
locally triggered manual switching tests between main and standby channels.
2. Field Boosting/Bucking Operations
Local Operation: Issue field boost or buck commands via the excitation
panel; commands are transmitted to the CPU, which modifies the voltage setpoint
and adjusts the excitation output. Remote Operation: The DCS system issues field
boost/buck commands via communication; the CPU receives and executes them while
applying command interlock logic (preventing further adjustment if limits are
exceeded).
.jpg)
3. Parameter Operations
Parameter Reading: Connect using host software tools to read operating
parameters, event waveforms, and fault records from the CPU. Parameter
Modification: Requires engineer-level privileges. After modification, download
the parameters to the CPU and save them; some critical parameters require a
board reboot to take effect.
Waveform Retrieval: The CPU features built-in fault waveform recording; it
automatically captures waveforms during excitation disturbances, trips, or
faults for post-event analysis.
4. Fault Reset Operation
Once the fault is cleared, a reset command can be issued via the local
panel or remotely; the CPU clears the fault alarm and resumes normal monitoring.
If a persistent hardware fault exists, the reset cannot be performed.
IV. Precautions
Power Supply: The board operates on 24V DC; power fluctuations must remain
within permissible limits. A UPS is recommended to prevent voltage dips from
damaging the board. Reverse polarity connection is strictly prohibited.
Electromagnetic Protection: Ensure the control cabinet is reliably grounded
and shielded cables are grounded at one end. Route high-power lines in the power
cabinet separately from low-voltage CPU sampling lines to prevent
electromagnetic interference (generated by thyristor switching) from causing
sampling distortion or control errors.
Electrostatic Protection: Wear an anti-static wrist strap when installing
or removing boards; do not touch chips or gold-plated edge connectors with bare
hands, as static electricity can instantly destroy the CPU chip. Store boards in
anti-static bags.
Channel Maintenance: During dual-channel operation, do not remove both CPU
boards simultaneously. Shut down the system or implement appropriate safety
measures before replacing boards; after replacement, verify the firmware version
and project parameters, and perform recalibration.
Firmware Version: When replacing a CPU, flash it with a firmware version
compatible with the original system; version mismatches can lead to
communication anomalies, control logic errors, or failure of channel
switching.
Parameter Management: Maintain backup files for all parameter
modifications. Do not arbitrarily modify PID settings, limits, or protection
setpoints while the unit is running, as this could cause unit oscillation or
over-excitation trips. Operational Monitoring: Regularly monitor the status
indicator lights on the boards; promptly check the event log if a red fault
indicator illuminates. CPU overheating will trigger an alarm; inspect the
cabinet fans and temperature control system.
Safety Isolation: During maintenance, ensure the board's power supply and
the CT secondary circuit are disconnected to prevent high voltage from entering
the board, which could cause equipment damage or personal injury.
V. Application Areas
Thermal Power Units: Serves as the main controller for the UNITROL
excitation system in steam turbine generators—its primary application
scenario.
Hydropower Units: Excitation regulation for large and medium-sized
hydro-generators, meeting the rapid response requirements of hydraulic
turbines.
Gas Turbine Power Projects: Excitation control for generators in
combined-cycle power plants.
.jpg)
Captive Power Plants: Internal generator units for steel, chemical, and
large-scale petrochemical enterprises.
New Energy-Supporting Peak-Shaving Plants: Excitation control for
synchronous generators in peak-shaving plants, supporting grid voltage
stability.
Overseas Power Projects: Excitation control systems for export-oriented
generator unit packages.
VI. Advantages and Features
High-Performance Computing: Features high-speed sampling and short control
cycles; the AVR offers rapid regulation response and strong voltage fluctuation
suppression, ensuring high stability during system disturbances.
Reliable Redundant Architecture: Supports dual-CPU redundancy with bumpless
channel switching; a single CPU failure does not trip the excitation system,
significantly enhancing the unit's continuous operation capability.
Comprehensive Limiting and Protection Algorithms: Includes a full suite of
built-in generator excitation limit models—such as V/Hz, over-excitation,
under-excitation, and stator current limits—to prevent operation outside
permissible ranges under various conditions. Integrates PSS (Power System
Stabilizer) to effectively suppress low-frequency power system oscillations.
Powerful Event Logging and Waveform Recording: Large-capacity event logging
with millisecond-level timestamps; built-in fault recording captures voltage,
current, and control signals, facilitating fault tracing and analysis.
Versatile Communication Interfaces: Supports multiple industrial
communication protocols for easy integration with power plant DCS and SCADA
systems, ensuring stable data exchange.
Modular Design: Features independent circuit boards for easy replacement
and maintenance; part of the UNITROL standard module series with a mature spare
parts ecosystem.Strong interference immunity: Industrial-grade hardware design
and wide operating temperature range make it suitable for power plant
environments characterized by dust, vibration, and strong electromagnetic
interference.
High configurability: Control logic, protection settings, and regulation
parameters can all be configured via software, allowing adaptation to generators
of various capacities and types, as well as flexible project implementation.
3BHE020455R0103 CPU Closed-Loop Regulation Calculation Process
I. Signal Acquisition and Pre-processing Stage (Pre-calculation phase)
The onboard A/D sampling circuit continuously acquires generator terminal
PT voltage, stator CT current, and rotor excitation current (from the power
cabinet shunt); simultaneously, it acquires binary signals such as generator
circuit breaker position, unit status, and channel status. The sampling cycle is
fixed by the CPU firmware, utilizing high-speed synchronous sampling to ensure
phase alignment between voltage and current.
Signal per-unit (p.u.) conversion: The CPU converts raw A/D values into
per-unit (p.u.) values based on project-preset PT and CT transformation
ratios; all subsequent regulation calculations are based on this per-unit
model.
Signal validation and filtering:
Validity check: Detects sudden jumps, wire breaks, or out-of-range
conditions in voltage/current signals. If a PT wire break is detected, the PT
wire break logic is automatically triggered, the AVR is blocked, and the system
can automatically switch to FCR (manual) mode.
Digital filtering: FIR digital filtering is employed to eliminate
high-frequency noise caused by electromagnetic interference, preventing jitter
in the regulation output; filtering parameters are configurable.
Calculation of auxiliary variables: Generator active power, reactive power,
and power factor are calculated from terminal voltage and stator current for use
in the PSS, under-excitation/over-excitation limiting, and stator current
limiting modules.
Upon completion of pre-processing, the following values are
obtained—actual terminal voltage (Ut_act), actual rotor current (If_act), active
power (P), and reactive power (Q)—and are fed into the closed-loop regulation
module.
II. Setpoint Generation Stage (Closed-loop Setpoint)
In AVR mode, the priority for the voltage setpoint (Ut_ref) source is:
Remote DCS setpoint > Local panel setpoint > Local raise/lower excitation
operation. Raise/lower operations essentially involve slowly modifying Ut_ref
subject to a rate-of-change limit (to prevent large excitation fluctuations
caused by sudden setpoint jumps). The setpoint is also subject to hard upper and
lower limits, ensuring it does not exceed the unit's permissible maximum and
minimum terminal voltage settings.
III. Outer Loop: AVR Voltage Closed-loop Calculation (Main Regulation
Loop)
AVR Objective: To maintain the generator terminal voltage (Ut) so that it
tracks the setpoint (Ut_ref).
Deviation Calculation:
\(e_{Ut}=U_{t\_ref}-U_{t\_act}\) where \(e_{Ut}\) is the voltage deviation,
Ut_ref is the voltage setpoint, and Ut_act is the measured terminal voltage. 2.
PID Calculation (UNITROL employs an incremental PID algorithm with integral
anti-windup; this is the core algorithm for this CPU).
P (Proportional) Term: Outputs a regulation value directly based on the
magnitude of the deviation, enabling rapid response to voltage deviations; the
proportional gain (Kp) is configurable.
I (Integral) Term: Eliminates steady-state voltage error. It includes
integral anti-windup (back-calculation); integration accumulation pauses when
the output is clamped, preventing integral saturation that could lead to
regulation overshoot. This is a critical design feature of the excitation
regulator, preventing voltage oscillations during major disturbances.
D (Derivative) Term: Suppresses dynamic fluctuations caused by rapid
voltage changes and dampens oscillations; the D term is generally small and may
be set to zero under certain operating conditions.
AVR Outer Loop Output: The AVR PID output serves as the setpoint (If_ref)
for the inner rotor current loop.
Simplified Concept: The voltage outer loop calculates the amount of rotor
current required to bring the terminal voltage back to the setpoint and outputs
this value to the inner rotor current loop. IV. Inner Loop: FCR Rotor Current
Closed-Loop Calculation (Current Inner Loop)
The current inner loop responds much faster than the voltage outer loop,
functioning as a high-speed servo loop. Its role is to precisely track the rotor
current setpoint ($I_{f\_ref}$) issued by the AVR outer loop and to reject
disturbances in the excitation power circuit (such as power supply fluctuations
or variations in thyristor voltage drops).
V. Limiter Module Intervention (Priority Higher Than Standard PID
Regulation)
While the dual-loop system operates normally, the CPU simultaneously runs
various limiters. These limiters function as protective closed-loop controls
with higher priority than standard AVR/FCR regulation. If the operating point
reaches a limit boundary, the limiter takes over the regulation setpoint,
forcing the unit back into the safe operating zone; the AVR is simultaneously
locked out by the limiter. The parallel limiter loops include:
Over-Excitation Limiter (OEL): Monitors generator rotor current; if the
current exceeds limits, the OEL output overrides the AVR setpoint to reduce
excitation current and protect the rotor from overheating.
Under-Excitation Limiter (UEL): Monitors active power and terminal voltage;
if the unit enters an excessive leading power factor (underexcited) state, the
UEL increases excitation to prevent loss of excitation.
V/Hz Limiter (Flux Limiter): If the voltage-to-frequency ratio exceeds
limits, the voltage setpoint is reduced to prevent over-fluxing of the generator
stator core.
Stator Current Limiter (SCL): If stator current exceeds limits, excitation
is reduced to limit stator heating.
Limiters also utilize independent PID closed-loop calculations; once
activated, they directly override the AVR outer loop output ($I_{f\_ref}$) to
prioritize protective regulation. Upon deactivation, the system smoothly reverts
to AVR regulation.
VI. PSS Power System Stabilizer Parallel Operation (Supplementary Damping
Branch; Does Not Replace Main Closed-Loop)
The PSS provides a supplementary control signal and does not participate in
the basic regulation of the main voltage closed-loop. The CPU acquires active
power (P) or rotor speed signals. After passing through DC-blocking and lead-lag
compensation stages, it generates an auxiliary PSS output (ΔUp), which is
superimposed onto the AVR voltage reference (Ut_ref). Function: When
low-frequency oscillations occur in the power grid, the PSS outputs an auxiliary
excitation modulation signal to introduce positive damping into the system,
thereby suppressing generator power oscillations. The PSS output is subject to
maximum amplitude limiting, ensuring it does not cause significant disturbances
to the generator terminal voltage reference.
VII. Output Limiting, Channel Processing, and Pulse Command Issuance
Hard limits are applied to the final firing angle command: minimum and
maximum firing angles are set to ensure the thyristors operate within a safe
range.
Dual-channel redundancy processing: The primary CPU performs the complete
closed-loop calculation and outputs firing commands; the standby CPU performs
synchronous sampling and executes the same closed-loop calculation, tracking the
primary channel's output in real-time. In the event of a primary CPU failure, a
bumpless transfer occurs, and the standby CPU's calculation results directly
take over pulse output.
The CPU transmits the calculated firing angle commands via the internal bus
to the pulse amplification board. Based on the firing angle, the pulse board
generates synchronized thyristor firing pulses to drive the thyristors in the
excitation power cabinet.
VIII. Feedback Update and Cyclic Calculation
The power cabinet executes the firing command → rotor excitation current
changes → generator magnetic field changes → generator terminal voltage (Ut)
changes → new voltage and current signals are fed to the CPU's sampling inputs,
initiating the next closed-loop calculation cycle. This closed-loop process
repeats continuously.
IX. Closed-Loop Calculation in Manual FCR Mode (Current-Only Closed-Loop;
AVR Outer Loop Disabled)
When switched to manual FCR mode, the AVR voltage outer loop is completely
disabled. The setpoint becomes the rotor current reference (If_ref), and the CPU
executes only the rotor current inner-loop PID control to maintain a constant
rotor current. In this mode, the terminal voltage varies with the generator
load; there is no automatic voltage regulation capability, and the mode is used
only for testing or as a backup during AVR failure.
X. Key Characteristics of Closed-Loop Computation (CPU Firmware
Features)
Multi-loop timing: The outer voltage loop operates on a slower cycle, while
the inner rotor current loop operates on a faster cycle; decoupling the fast and
slow loops ensures stability.
Integral anti-windup is central: When a limiter activates or the output
reaches its limit, integral accumulation halts to prevent significant voltage
overshoot the moment the system exits the limiting state.
Smooth switching logic: During AVR↔FCR transitions or main/standby channel
switching, the CPU performs output tracking to ensure there are no abrupt
changes in the control signal at the moment of transfer, thereby achieving
bumpless switching.
All intermediate variables in the computation process (error, PID output,
PSS output, limiter status) are stored in memory in real-time to serve as event
recording data.
Recommended related products:
3BHE030410R3011 PPD113
PPD113B03 3BHE030410R3011
PPD113B03-20-110110 3BHE023584R204Z
3BHE023584R204Z PPD113
PPD113B01-10-150000 3BHE023784R1023
PPD113B03-26-100110 3BHE023584R2634
3BHE023584R2634 PPD113
PPD113B01-25-111000 3BHE023784R2530
3BHE023784R2530 PPD113
3BHE017628R0002 PPD115
3BHE017628R0102 PPD115
PPD115A102 3BHE017628R0102
PPD117A3011 3BHE030410R3011
3BHE040375R1023 PPD512
PPD512A10-15000 3BHE040375R1023
PPD512A10-454000 3BHE040375R103E
3BHE039724R0C4A PP D513A0C
PP D513 A0C-110440 3BHE039724R0C4A
PPD513 A0E-110110 3BHE039724R0E41
3BHE039724R0E41 PPD513
More......